Most heat pump quotes look reasonable on the page: a named unit, a cylinder, a price and a grant deduction. The problems sit in the design behind the quote, which homeowners are rarely shown. A unit that is too big or too small, radiators that cannot heat the room at a low flow temperature, and a unit placed where it is loud or short of air all appear as a single line item.
This guide covers the engineering side. It explains what a design review checks, which signs justify paying for one, and when to keep your money. For the commercial side (what is included, excluded and how the price breaks down), use my heat pump quote checklist.
Heat pump design review in short
- A quote is not a design. The faults that cost you money (wrong size, radiators too small, a badly placed unit) hide behind single line items.
- Ask for three documents: the room-by-room heat loss calculation, the radiator schedule at the design flow temperature, and the unit and cylinder positions.
- The radiators are where designs most often fall short. A design that runs at 55°C to make old radiators work will cost more every year.
- Two or more of the six warning signs below make an independent review worth paying for, before you pay a deposit.
- Skip the review if the installer has already shown you consistent figures, or you are still collecting rough estimates.
Why a quote can look sensible and still be badly designed
A quote describes what you will be sold. A design describes what the system must do in your house on the coldest realistic day, and whether the equipment can do it. Many quotes are produced with the design half finished, or with a design that is little more than a model number.
Neither has to involve dishonesty. An installer who sizes from the old boiler’s output, or from a rule of thumb per square metre, is working from habit. The price still looks competitive, because skipping the detailed work makes a quote cheaper to produce.
Why heat pumps are less forgiving than boilers
A boiler can make up for undersized radiators by running hotter. A heat pump loses efficiency as the flow temperature rises, so a radiator shortfall a boiler would hide shows up as higher bills, or a house that never quite warms up.
Six warning signs in a heat pump design that justify a second opinion
Any one of these is a reason to ask questions. Two or more is a reason to pay for a review.
- No room-by-room heat loss calculation
You have one kilowatt figure for the whole house, or you are told the size is “standard for a house like yours”.
- The size came before the survey
A unit size quoted from a phone call, the floor area or the old boiler’s rating means the calculation came second, if at all.
- “Radiators retained”, with no figures
Nobody has shown what each existing radiator will give out at the new, lower flow temperature.
- No flow temperature, or 55°C or more
A high design flow temperature with no reason given usually means the radiators were not sized properly.
- A cylinder picked off the shelf
No mention of how many people live there, bath use or a second bathroom, and no heat pump coil size.
- A unit position chosen for convenience
No word on noise at the neighbours’ windows, airflow or how long the pipe run is.
Two more: an efficiency figure with no stated basis, and a designer who cannot or will not share the calculation. A competent designer has the numbers on file and can send them the same day. To check the installer as well as the design, see choosing the right heat pump installer.
The heat loss calculation: what it should show and what rule-of-thumb sizing hides
A proper calculation works through the house one room at a time and gives a figure in watts for each room, plus a total in kilowatts. That total is what the heat pump must meet, and the room figures are what the radiators are sized against, so you should be able to see both.
| Section of the calculation | What it should show | What to check against your house |
|---|---|---|
| Room dimensions | Floor area, ceiling height and outside wall area for every room | Measure two or three rooms yourself; errors carry straight through |
| Fabric | Wall, floor, roof and window types, each with a U-value | Solid brick recorded as filled cavity, or single glazing as double, are common mistakes |
| Air leakage | An air change rate for each room or the whole house | Open chimneys, old sash windows and draughty floors all raise it |
| Temperatures | An outdoor design temperature for your area and a target for each room | Living rooms and bathrooms are usually set warmer than bedrooms |
| Result | Watts for each room and a total in kilowatts | The unit size should be close to the total, not rounded well up |
| Assumptions | Whether it is the house as it is now or after planned insulation | Either can be right, but the design must say which |
MCS requires a room-by-room heat loss calculation, normally to the BS EN 12831 method, for any installation that claims the Boiler Upgrade Scheme.
What rule-of-thumb sizing hides:
Oversized
Switches on and off more often, which cuts efficiency and adds wear. It also costs more to buy.
Undersized
On cold days the backup heater or immersion fills the gap at full electricity prices.
Wrong house
A wrongly recorded wall, window or room size passes straight into the final figure, however careful the maths.
Planning to insulate first? See how to prepare your home for a heat pump, and make sure the design states which version of the house it assumes.
Radiators and flow temperature: where designs most often fall short
This is where I would look first. Radiators are rated at boiler temperatures. At the lower flow temperatures where a heat pump runs best, the same radiator gives out much less heat, so one that heated a room comfortably from a boiler may fall well short at 45°C.

A sound design includes a room schedule like this one:
| Room | Heat loss | Radiator | Output at 45°C flow | Result |
|---|---|---|---|---|
| Living room | 1,450 W | Existing double panel, 1200 x 600 | about 700 W | Short: larger or extra radiator |
| Kitchen | 600 W | Existing double panel, 1000 x 600 | about 600 W | Meets it: keep |
| Main bedroom | 500 W | Existing single panel, 1000 x 600 | about 320 W | Short: change to double panel |
| Bathroom | 400 W | Existing towel rail | about 150 W | Short: larger rail or add a radiator |
An illustration of the layout to ask for, not figures for your house. A radiator gives roughly a third to two fifths of its catalogue output (rated at a 50°C difference) when the flow is 45°C.
The usual fixes are larger radiators, double panels in place of single, fan-assisted radiators where space is tight, or underfloor heating where floors are coming up anyway. For the trade-offs, see underfloor heating or radiators with a heat pump and my radiators guide.
Watch for a design that keeps the flow temperature high to make the old radiators work. It may heat the house, but efficiency suffers all year, and the running cost estimate may not reflect it. Ask what flow temperature the design assumes, what efficiency follows from it, and how the weather compensation will be set. A controller that handles weather compensation well matters here: see the best smart thermostats for heat pumps.
Cylinder, pipework and unit position: the details that decide noise and efficiency
These look like installation details rather than design, which is why they are easy to overlook.
| Decision | What a good design states | Why it matters |
|---|---|---|
| Cylinder | Make, size in litres and coil area, how the size was worked out from occupancy, and the schedule for heating it to 60°C to control legionella | Too small and the immersion runs often; too big and it loses heat and takes space |
| Pipework | Pipe sizes from the unit to the cylinder and system, the run length, and how outdoor or buried pipes are insulated | Heat pumps move several times more water than boilers; old 15mm or 22mm runs can starve the unit |
| Unit position | Clearances for airflow, the base, the condensate drain, and a noise check at the nearest neighbour’s window | A unit that recirculates its own cold air, or annoys the neighbours, never runs as designed |
| Buffer tank | Whether one is included, and why | Some systems need one, many do not; an unneeded tank adds cost and heat loss |
| Controls | Weather compensation curve, thermostat and cylinder control | The settings decide whether the design flow temperature is used at all |

Planning in England: most homes can fit an air source heat pump under permitted development. Since May 2025 there is no longer a 1 metre boundary rule, but the unit must meet the MCS 020 noise limit of 42 dB at the nearest neighbour’s window, and size and siting conditions still apply. Listed buildings and some conservation area sites need permission. My guide to how loud a heat pump is explains the noise check.
For cylinder choice, see the best hot water cylinders for heat pumps. If a buffer tank is included, read do you need a buffer tank with your heat pump? before you accept it.
What an independent design review covers, what you hand over and what you get back
A review is a qualified heating engineer working through the installer’s design to check that the numbers hold together. It is not a new quote, and nobody is selling you equipment.
What you hand over
- The quote and any design or specification
- The heat loss calculation, with room figures
- The radiator schedule
- Floor plans or sketches with the unit and cylinder marked
- Data sheets for the unit and cylinder
- What you know of the house: age, walls, insulation, glazing, occupants
What gets checked
- Heat loss inputs against the real building
- Unit size against the result
- Each radiator against its room at the design flow temperature
- Cylinder, pipework and controls against the unit
- Position for airflow, noise and pipe length
What you get back
- A written report separating clear errors from judgement calls
- Revised figures wherever something is wrong
- A short list of specific questions to put to the installer

If the installer has not provided a calculation, that is itself a finding, and the reviewer may do one from your plans. A review can change the unit size, the radiator schedule, the flow temperature, the cylinder or the unit position. Before you commit, ask for a fixed fee and a written scope, and check whether a site visit is included.
When a review is not worth paying for, and what to do if the designer disagrees
Worth paying for
- Two or more of the six warning signs
- A preferred installer whose design you cannot check yourself
- An older house with solid walls, high ceilings or mixed extensions
- Quotes that differ by several kilowatts for the same house
Probably not worth it
- You already have a full room-by-room calculation, radiator schedule and flow temperature that match your house
- You are still collecting rough estimates: wait for a proper design to check
- A small, simple job where the fee would be a large share of any saving
If the review finds problems and the designer disagrees, treat it as a technical discussion about specific numbers. Send the points that matter (the wall U-value used, the radiator outputs at the design flow temperature, the cylinder sizing basis) and ask for a written answer to each. Often an input was simply entered wrongly and is corrected without argument.
If the designer defends the design with reasons that hold up, you now know why, and that is worth having. If the answers are vague, or a clearly wrong figure will not be revised, that tells you how the installation will be handled. Do not pay a deposit until the disputed points are settled in writing. If they cannot be, get another installer’s survey and review it the same way.
Common questions
Heat pump design reviews: common questions
Is my installer required to give me the heat loss calculation?
An MCS-certified installer must carry out a room-by-room heat loss calculation, and you are entitled to ask for it. A good installer will send it without fuss; reluctance to share it is itself a warning sign.
What flow temperature should a heat pump design use?
There is no single right figure, but 45°C or lower is a good sign and 35°C to 40°C is possible with underfloor heating or generous radiators. Above 50°C, ask why, and what it does to the running cost estimate.
Can a review be done without a site visit?
Yes, most reviews work from documents and photographs. Confirm before you pay whether a visit is included, and if the installer has done no calculation, the reviewer may need plans or a visit to do one.
What if the installer disagrees with the review?
Send the specific points (a U-value, a radiator output, the cylinder sizing basis) and ask for a written answer to each. Wrong inputs are usually corrected without argument.
Do I still need planning permission for an air source heat pump?
In England most homes can fit one under permitted development, provided the unit meets the MCS 020 noise limit of 42 dB at the nearest neighbour’s window and the other size and siting conditions. The old 1 metre boundary rule was removed in 2025. Listed buildings and some conservation area sites still need permission.